EasyManua.ls Logo

Rotex GCU compact - After Start-Up

Rotex GCU compact
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
ROTEX GCU compact - 
5 x Start-up
6. In the programme [Emission Measurement] select the setting
[Base Load] (see chapter 15.2), but do not confirm.
Make sure the heat can dissipate into the heating network
during emission meas
urement.
Ɣ Use the flue gas analyser to check the burner settings and
compare them with tab. 5-1 to tab. 5-3.
a) If the O
2
/CO
2
concentrations lie within the permissible
values:
Î No additional measures are required.
b) If the O
2
/CO
2
concentrations lie outside the permissible
values:
Î Carry out 100% calibration and adjust the [Drop Io-base]
in such a way that the setting range is reached (see
chapter 7.3.4) and repeat the measurement from step 5.
Ɣ Document the measured
values in the "Installation certifi-
cation" and in the operating manual.
7. End programme [Emission Measurement].
8. Set manual mode from the RoCon BF control (see operating
instructions "RoCon BF Control").
9. Check the resistance in the flue gas line (see chapter 4.5).
5.1.4 After start-up
Ɣ Mount the sound insulation hood (see chapter 4.4.3).
Ɣ Check all items on the "Checklist after start-up" (see
section 5.2).
Ɣ Log the test results on the checklist
.
Only when it is possible to answer all items on the checklist
with Yes, i
s it allowed to hand over the ROTEX GCU compact
to the operator.
CAUTION!
The firing unit is programmed to take into
account the ageing of th
e components.
A 100 % calibration of the firing unit can have
a negative impact on th
e above even if the
exhaust setting values (tab. 5-1 to tab. 5-3) are
adhered to.
Ɣ Only carry out a calib
ration of the firing unit
when the exhaust setting values are not
adhered to, or when a mechanical change
was carried out, e.g. by replacing the
component with original ROTEX spare
parts.
Type GCU compact 315 / 515 (BIV)
Gas type
(Prüfgas)**
Burner load O
2
-content
in %
CO
2
-content
in %
Natural gas E/H
(G20)
Base Load 4.0 - 5.5 8.6 - 9.5
Full Load 4.0 - 5.4 8.7 - 9.5
Natural gas
LL
/L (G25)
Base Load 4.0 - 5.5 8.5 -
9.3
Full Load 4.0 - 5.4 8.5 - 9.3
Propane*
(G
31)
Base Load 4.0 - 5.5 10.0 -
11.2
Full Load 4.0 - 5.4 10.2 - 11.2
* Liquid gas setting
** Compare with the information on the yellow sticker attached to the burner
housing
Tab. 5-1 Start-up control values for GCU compact 315 and GCU
compact 515 for various gas types
Type GCU compact 324/ 524 (BIV)
Gas type (test
gas)**
Burner load O
2
-content
in %
CO
2
-content
in %
Natural gas E/H
(G20)
Base Load 4.0 - 5.5 8.6 - 9.5
Full Load 3.8 - 5.1 9.0 - 9.6
Natural gas
LL/L (G2
5)
Base Load 4.0 - 5.5 8.5 - 9.3
Full Load 3.8 - 5.1 8.7 - 9.4
Propane*
(G31)
Base Load 4.0 - 5.5 10.0 - 11.2
Full Load 3.8 - 5.1 10.4 - 11.3
* Liquid gas setting
** Compare with the information on the yellow sticker attached to the burner
housing
Tab. 5-2 Start-up control values for GCU compact 324 and GCU
compact 524 for various gas types
Type GCU compact 533 (BIV)
Gas type (test
gas)**
Burner load O
2
-content
in %
CO
2
-content
in %
Natural gas E/H
(G20)
Base Load 4.0 - 5.5 8.6 - 9.5
Full Load 3.5 - 4.9 9.0 - 9.8
Natural gas
LL
/L (G2
5)
Base Load 4.0 - 5.5 8.5 - 9.3
Full Load 3.5 - 4.9 8.8 - 9.5
Propane*
(G31)
Base Load 4.0 - 5.5 10.0 - 11.2
Full Load 3.5 - 4.9 10.5 - 11.4
* Liquid gas setting
** Compare with the information on the yellow sticker attached to the burner
housing
Tab. 5-3 Start-up control values for GCU compact 533 for various gas
types

Table of Contents