VM1000 Series
‐100‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
FA.13
Fault protection
action option 1
0: Coast to stop
1: Stop as setting of stop mode
2: Operation continue
Units: Motor overload(Err11)
Tens: Input phase-loss(Err12)
Hundreds: Output
phase-loss(Err13)
Thousands: External fault(Err15)
Tens of Thousand:
Communication Error(Err16)
11111 0 ☆
FA.14
Fault protection
action option 2
0: Coast to stop
1: Stop as setting of stop mode
2: Operation continue
Units: Reserved
Tens: Parameter Re-write
failure(Err21)
Hundreds: Reserved
Thousands: Reserved
Tens of Thousand: accumulative
running time reached(Err16)
11111 0 ☆
FA.15
Fault protection
action option 3
0: Coast to stop
1: Stop as setting of stop mode
2: Operation continue
Units: User defined fault 1 (Err27)
Tens: User defined fault 2 (Err28)
Hundreds: Reserved
Thousands: Load loss(Err30)
Tens of Thousand: PID feedback
loss during operation(Err31)
11111 0 ☆