VM1000 Series
‐101‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
FA.16
Fault protection
action option 4
0: Coast to stop
1: Stop as setting of stop mode
2: Operation continue
Units: Motor speed deviation too
large (Err42)
Tens: Motor over speed (Err43)
Hundreds: Initial position
error(E51)
Thousands: Reserved)
Tens of Thousand: Reserved
11111 0
FA.17 Reserved
FA.18
Under-voltage
setting
60.0%~140.0% 0.10% 100.00%
FA.19
Over-voltage
setting
200.0V~2500.0V 0.1V 810
FA.20
Frequency option
for
continuing to run
upon fault
0: Current running frequency
1: Selected frequency reference
2: Upper limit frequency
3: Lower limit frequency
4: Preset backup freqency in
abnormal condition
1 0
FA.21
Preset backup
freqency in
abnormal condition
0.0%~100.0%(Current target
frequency)
0.10% 100.00%
FA.22
Action at
instantaneous
power failure
0: No action
1: Deceleration
2: Deceleration and stop
1 0
FA.23
Action pause
voltage at
instantaneous
power failure
80.0%~100.0% 0.10% 90.00%