VM1000 Series
‐102‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
FA.24
Voltage
recoverring time at
instantaneous
power failure
0.00s~100.00s 0.01s 0.50s ☆
FA.25
Action start voltage
at instantaneous
power failure
60.0%~100.0%(Standard DC bus
voltage)
0.10% 80.00% ☆
FA.26
Load loss
protection
0: Disable
1: Enable
1 0 ☆
FA.27
Load loss detection
level
0.0~100.0% 0.10% 10.00% ☆
FA.28
Load loss detection
time
0.0~60.0s 0.1s 1.0s ☆
FA.29
Decimal place of
frequency at fault
1: 1 decimal place
2: 2 decimal place
Units: Frequency decimal place of
the last fault
Tens: Fequency decimal place of
the fault before last
Hundreds: Fequency decimal
place of the second fault before
last
1 222 ●
FB Group: Swing frequency, length control and counter control
FB.00
Swing frequency
setting mode
0: Relative to center frequency
1: Relative to Maximum
frequency
1 0 ☆
FB.01
Swing frequency
range
0.0%~100.0% 0.10% 0.00% ☆
FB.02
Skip frequency
range
0.0%~50.0% 0.10% 0.00% ☆