VM1000 Series
‐62‐
4.5 Auto-tuning of Motor Parameters
Selection of vector control modeBefore the drive operates ,you must input the
exact nameplate parameters of motor, the standard motor parameters is equipped
with 8000H inverter according to parameters on the nameplate; vector control has a
high dependence on motor parameters.In order to get good control performance,it
must receive the correct parameters of controlled motor.
Procedures of motor auto tuning are as follows:
First, the control command source (F0.02) is selected as keypad.
Then input the following parameters according to the actual motor parameters
(according to the current motor selection):
F2.00: GP Type Display Selection
F2.01: motor rated power
F2.02: motor rated voltage
F2.03: motor rated current
F2.04: motor rated frequency
F2.05: motor rated speed
If the motor is completely disconnected from the load, select 2 in F2.11 (auto-tuning
completely), and then press the “RUN ”on the keypad , the VFD will automatically
calculate following parameter of the motor:
F2.06: asynchronous motor stator resistance
F2.07: asynchronous motor rotor resistance
F2.08: asynchronous motor leakage inductance
F2.09: asynchronous mutual inductance
F2.10: Motor no load current
The motor parameter automatic tuning above is completed
If the motor can not be completely disconnected with load, select 1 in the F2.11
(static auto tuning), and then press the RUN key on the keyboard.