4.5 Auto-tuning of Motor Parameters
Selection of vector control mode:Before the drive operates ,you must input the
exact nameplate parameters of motor, the standard motor parameters is equipped
with 8000H inverter according to parameters on the nameplate; vector control has a
high dependence on motor parameters.In order to get good control performance,it
must receive the correct parameters of controlled motor.
Procedures of motor auto tuning are as follows:
First, the control command source (F0.02) is selected as keypad.
Then input the following parameters according to the actual motor parameters
(according to the current motor selection):
F2.00: GP Type Display Selection
F2.01: motor rated power
F2.02: motor rated voltage
F2.03: motor rated current
F2.04: motor rated frequency
F2.05: motor rated speed
If the motor is completely disconnected from the load, select 2 in F2.11 (auto-tuning
completely), and then press the “RUN ”on the keypad , the VFD will automatically
calculate following parameter of the motor:
F2.06: asynchronous motor stator resistance
F2.07: asynchronous motor rotor resistance
F2.08: asynchronous motor leakage inductance
F2.09: asynchronous mutual inductance
F2.10: Motor no load current
The motor parameter automatic tuning above is completed
If the motor can not be completely disconnected with load, select 1 in the F2.11
(static auto tuning), and then press the RUN key on the keyboard.