VM1000 Series
‐68‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
F0.06
Auxiliary
Frequency
Reference Y's
Scope Setting
while in
superposition of X
and Y
0%~150% 1% 100% ☆
F0.07
Frequency
References
Superposition
Selection
Units: Frequency Reference
Selection
0: Master Frequency Reference X
1: Calculation of Master with
Auxiliary Frequency
Reference(Calculation defined by
setting of tens)
2: Switching between Master and
Auxiliary Frequency Reference.
3: Switching between Master and
Calculation of Master with
Auxiliary Frequency Reference
4: Switching between Auxiliary
and Calculation of Master with
Auxiliary Frequency Reference
Tens: Calculation Definision of
Master and Auxiliary
0: Master+Auxiliary
1: Master-Auxiliary
2: Maximium Value between the
Two
3: Minimium Value between the
Two
11 0 ☆
F0.08 Preset Frequency
0.00Hz~Maximium Frequency
F0.10
0.01Hz 50.00Hz ☆
F0.09
Running Direction
Selection
0:Forward
1:Reverse
1 0 ☆