VM1000 Series
‐76‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
F3.18
Integral gain of M
axis current loop
0~60000 1 1300 ☆
F3.19
Proportional gain
of T axis current
loop
0~60000 1 2000 ☆
F3.20
Integral gain of T
axis current loop
0~60000 1 1300 ☆
F3.21
Speed loop integral
seperation
0: Invalid
1: Valid
1 0 ☆
F4 Group: V/F Control Parameters
F4.00
V/F curve & mode
selection
0: Linear V/F curve
1: Multi-point V/F curve
2: Square V/F curve
3~9: Reserved
10: V/F complete seperation mode
11: V/F half seperation mode
1 0 ★
F4.01 Torque boost
0.0%:Automatic torque boost
0.1%~30.0% (Invalid when in V/F
seperation mode
0.10%
Rated
Model
Dependent
☆
F4.02
Torque boost
cut-off frequency
0.00Hz~Maximum Frequency 0.01Hz 50.00Hz ★
F4.03
Multi-point V/F
curve's frequency
point 1
0.00Hz~F4.05 0.01Hz 0.00Hz ★
F4.04
Multi-point V/F
curve's voltage
point 1
0.0%~100.0% 0.10% 0.00% ★