VM1000 Series
‐78‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
F4.13
Digital setting for
voltage reference in
V/F seperation
mode
0V~Motor rated voltage 1V 0V ☆
F4.14
Voltage rising time
for V/F seperation
mode
0.0s~1000.0s
(Time from 0V to motor rated
voltage.)
0.1s 0.0s ☆
F5 Group: Input Terminals Parameters
F5.00
DI1 terminal
function
0: No function
1: Run forward(FWD)
2: Run reverse(REV)
3: 3-wire control
4: Jog forward (FJOG)
5: Jog reverse (RJOG)
6: UP command
7: DOWN command
8: Coast to stop
9: Fault reset (RESET)
10: Pause running
11: External fault input N. O.
12: Multi-step speed terminal 1
13: Multi-step speed terminal 2
14: Multi-step speed terminal 3
15: Multi-step speed terminal 4
16: Acceleration/Deceleration
Time Selection Terminal 1
17: Acceleration/Deceleration
Time Selection Terminal 2
18: : Frequency Reference
Switching Terminal
19: Reset UP/DOWN Frequency
Setting(Both keypad and
terminals)
1 1 ★
F5.01
DI2 terminal
function
1 2 ★
F5.02
DI3 terminal
function
1 9 ★