VM1000 Series
‐79‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
F5.03
DI4 terminal
function
20: Control Command Switching
Terminal 1
21: Acceleration/deceleration
prohibited
22: PID Control Pause
23:Simple PLC Running Status
Reset
24:Swing Frequency Pause
25: Counter Input
26: Counter Reset
27: Length Counting Input
28: Length Counting Reset
29: Torque Control Prohibit
30:PULSE Input(High Frequency
Input, DI6 terminal only)
31: Reserved
32: DC Brake Instantly
33: External Fault Input N.C.
34: Frequency Setting Taking
Effect(If no terminal is set to this
value, the function is in effect
defaultly)
35: PID Control Output Reverse
36: External Stop terminal 1
37: Control Command Switching
terminal 2
38: PID Integration Pause
39: Switching terminal, between
Frequency Reference X and Preset
Frequency
40: Switching terminal, between
Frequency Reference Y and Preset
Frequency
41~42: Reserved
43: PID Parameter Switching
Terminal
44: User Defined Fault 1
44: User Defined Fault 2
1 0 ★
F5.04
DI5 terminal
function
1 0 ★
F5.05
DI6 terminal
function
1 0 ★