VM1000 Series
‐81‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
F5.23 AI2 lower limit 0.00V ~ F5.25 0.01V 0.00V ☆
F5.24
Setting value
corresponding to
AI2 lower limit
-100.0% ~ +100.0% 0.10% 0.00% ☆
F5.25 AI2 upper limit F5.23 ~ +10.00V 0.01V 10.00V ☆
F5.26
Setting value
corresponding to
AI2 upper limit
-100.0% ~ +100.0% 0.10% 100.00% ☆
F5.27 AI2 filter time 0.00s ~ 10.00s 0.01s 0.10s ☆
F5.28
PULSE input lower
limit
0.00kHz ~ F5.30
0.01kH
z
0.00kHz ☆
F5.29
Setting value
corresponding to
PULSE input lower
limit
-100.0% ~ 100.0% 0.10% 0.00% ☆
F5.30
PULSE input upper
limit
F5.28 ~ 100.00kHz
0.01kH
z
50.00kHz ☆
F5.31
Setting value
corresponding to
PULSE input upper
limit
-100.0% ~ 100.0% 0.10% 100.00% ☆
F5.32 PULSE filter time 0.00s ~ 10.00s 0.01s 0.10s ☆
F5.33 DI1 ON delay 0.0s ~ 3600.0s 0.1s 0.0s ★
F5.34 DI2 ON delay 0.0s ~ 3600.0s 0.1s 0.0s ★
F5.35 DI1 OFF delay 0.0s ~ 3600.0s 0.1s 0.0s ★