VM1000 Series
‐82‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
F5.36 DI2 OFF delay 0.0s 3600.0s 0.1s 0.0s
F5.37
DI input ON
status setting 1
0: High level
1: Low level
Unit: DI1
Tens: DI2
Hundreds: DI3
Thousands: DI4
Tens thousands: DI5
11111 0
F5.38
DI input ON status
setting 2
0: High level
1: Low level
Unit: DI6
Tens: Reserved
Hundreds: Reserved
Thousands: Reserved
Tens thousands: Reserved
11111 0
F6 Group: Output Terminals Parameters
F6.00
FM terminal output
selection
0: Pulse output(FMP)
1: Open collector discrete
output(FMR)
1 0
F6.01
FMR open
collector output
function
0: No output
1: AC drive running
2: Fault output (stop)
3: Frequency-level detection
FDT1 output
4: Frequency reached
5: Zero-speed running (no output
at stop)
6: Motor overload pre-warning
7: AC drive overload pre-warning
8: Set count value reached
9: Designated count value reached
10: Length reached
1 0
F6.02
Relay 1 output
function
1 2