EasyManua.ls Logo

SAJ VM1000 - Page 93

SAJ VM1000
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VM1000 Series
‐92‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
F8.11
Jump frequency
width
0.00Hz~Maximum Frequency 0.01Hz 0.00Hz
F8.12
FWD/REV
switchover dead
zone time
0.0s~3000.0s 0.1s 0.0s
F8.13 Reverse option
0: Reverse allowed
1: Reverse Prohibited
1 0
F8.14
Carrier Frequency
adjusting by
temperature
0: Disable
1: Enable
1 1
F8.15 Droop control 0.00Hz~10.00Hz 0.01Hz 0.00Hz
F8.16
Accumulative
power-on time
threshold
0h 65000h 1h 0h
F8.17
Accumulative
running time
threshold
0h 65000h 1h 65000h
F8.18
Drive startup
protection
0: Disable
1: Enable
1 0
F8.19
Frequency
detection value
(FDT1)
0.00Hz~Maximum Frequency 0.01Hz 50.00Hz
F8.20
Frequency
detection
hysteresis (FDT 1)
0.0%~100.0% (FDT1 Level) 0.10% 5.00%
F8.21
Detection width of
frequency
reached
0.0% 100.0% (Maximum
frequency)
0.10% 0.00%

Related product manuals