F8.11
Jump frequency
width
0.00Hz~Maximum Frequency 0.01Hz 0.00Hz ☆
F8.12
FWD/REV
switchover dead
zone time
0.0s~3000.0s 0.1s 0.0s ☆
F8.13 Reverse option
0: Reverse allowed
1: Reverse Prohibited
1 0 ☆
F8.14
Carrier Frequency
adjusting by
temperature
0: Disable
1: Enable
1 1 ☆
F8.15 Droop control 0.00Hz~10.00Hz 0.01Hz 0.00Hz ☆
F8.16
Accumulative
power-on time
threshold
0h ~ 65000h 1h 0h ☆
F8.17
Accumulative
running time
threshold
0h ~ 65000h 1h 65000h ☆
F8.18
Drive startup
protection
0: Disable
1: Enable
1 0 ☆
F8.19
Frequency
detection value
(FDT1)
0.00Hz~Maximum Frequency 0.01Hz 50.00Hz ☆
F8.20
Frequency
detection
hysteresis (FDT 1)
0.0%~100.0% (FDT1 Level) 0.10% 5.00% ☆
F8.21
Detection width of
frequency
reached
0.0% ~ 100.0% (Maximum
frequency)
0.10% 0.00% ☆