VM1000 Series
‐98‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
F9.24 PID integral option
Units: Seperated Integral
calculation
0: Disable
1: Enable
Tens: Output reaching limit and
stopping integral
0: Continue integral
1: Stop integral
11 0 ☆
F9.25
PID feedback loss
detection
0.0%: No detection
0.1% ~ 100.0%
0.10% 0.00% ☆
F9.26
PID feedback loss
detection time
0.0s~20.0s 0.1s 0.0s ☆
F9.27 PID option at stop
0: No calculation cotinue at stop
1: Calculation continue at stop
1 0 ☆
F9.28
PID auxiliary
function
0: Normal PID
1: PID with sleeping function
1 0 ☆
F9.29
PID sleeping
threshold
0.0%~100.0% 0.10% 60.00% ☆
F9.30 PID sleeping delay 0.0~3600.0s 0.1s 3.0s ☆
F9.31
PID wakeup
threshold
0.0%~100.0% 0.10% 20.00% ☆
F9.32 PID wakeup delay 0.0~3600.0s 0.1s 3.0s ☆
FA Group: Protection Parameters and Fault Record
FA.00
Motor overload
protection
0: Disable
1: Enable
1 1 ☆
FA.01
Motor overload
protection gain
0.20~10.00 0.01 1 ☆