VM1000 Series
‐97‐
Function
code
Description Set range Unit Default
Modifi
-cation
level
F9.13
PID output filter
time
0.00~60.00s 0.01s 0.00s
F9.14
Proportional gain
P2
0.0~100.0 0.1 20
F9.15 Integral time I2 0.01s~10.00s 0.01s 2.00s
F9.16
Differential time
D2
0.000s~10.000s 0.001s 0.000s
F9.17
PID control
parameter
switching function
0: No switching
1: Switching by DI terminal
2: Switching by deviation
1 0
F9.18
PID control
parameter
switching deviation
1
0.0%~F9.19 0.10% 20.00%
F9.19
PID control
parameter
switching deviation
2
F9.18~100.0% 0.10% 80.00%
F9.20
PID initial output
value
0.0%~100.0% 0.10% 0.00%
F9.21
PID initial output
time
0.00~650.00s 0.01s 0.00s
F9.22
Maximum positive
deviation limit of
output interval
0.00% 100.00% 0.01% 1.00%
F9.23
Maximum positive
deviation limit of
output interval
0.00%~100.00% 0.01% 1.00%