114 EB 8384-2 EN
Operating the positioner
7.9 Reset to default settings
This function resets all start-up and setting parameters as well as the diagnosis to the factory
defaultsettings(seecodelistinsection11.5).
Enable conguration:
Ifnosettingsareenteredwithin120seconds,theenabledcongurationfunctionbecomesin-
valid.
1. Turn untilCode3appears(reading:
No).
2. Press , the code number 3 blinks.
3. Turn
until YES appears.
4. Press
toconrm(reading: ).
Enableconguration
Default: No
Reset start-up parameters:
1. Turn untilCode36appears(reading:
••–••–).
2. Press , the code number 36 blinks.
3. Turn
until Std appears.
4. Press
toconrm.Allstart-upparameters
as well as the diagnosis are reset to their
default values.
Reset
Default: No
Code 36 - diAG allows just the diagnosis data (EXPERTplus) to be reset. Refer to the Operat-
ing Instructions for EXPERTplus valve diagnostics u EB8389.