EB 8384-2 EN 119
Servicing
8 Servicing
The positioner was checked by SAMSON
before it left the factory.
The product warranty becomes void if ser-
vice or repair work not described in these
instructions is performed without prior
agreement by SAMSON's After-sales Ser-
vice department.
Only use original spare parts by
SAMSON, which comply with the original
specications.
The positioner does not require any mainte-
nance.
Housing cover
Occasionally, the window in the cover may
need to be cleaned.
Incorrect cleaning will damage the window.
The window is made of Makrolon
®
(new de-
sign) and will be damaged when cleaned
with abrasive cleaning agents or agents con-
taining solvents.
Do not rub the window dry.
Do not use any cleaning agents containing
chlorine or alcohol or abrasive cleaning
agents.
Use a non-abrasive, soft cloth for cleaning.
Filters
Therearelterswitha100µmmeshsizein
the pneumatic connections for supply and
output which can be removed and cleaned,
if required.
Supply air pressure reducing stations
The maintenance instructions of any up-
stream supply air pressure reducing stations
must be observed.
8.1 Firmware update
Firmware updates on positioners currently
in operation can be performed as
described below. Only individuals with a
written approval may perform updates.
Approved individuals are named by
SAMSON's Total Quality Management and
assigned a test mark.
Laptops and computers connected to the
power supply must only be interconnected
with intrinsically safe equipment if the
SAMSON isolated USB interface adapter
(order no. 1400-9740) is connected in-
between for software programming or test
routines.
Updates outside the hazardous area:
Î Removethepositionerandperformthe
update outside the hazardous area.
Updates on site:
Î Updates on site are only permitted after
the plant operator presented a signed
hot work permit.
Note
NOTICE
!

Table of Contents

Other manuals for Samson 373 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samson 373 Series and is the answer not in the manual?

Samson 373 Series Specifications

General IconGeneral
BrandSamson
Model373 Series
CategoryValve Positioners
LanguageEnglish

Related product manuals