EB 8384-2 EN 121
Malfunctions
9 Malfunctions
Malfunctions are indicated on the display by
errorcodes.Section11.4listspossibleerror
messages and recommended action.
The error codes appear on the display corre-
spondingtotheirstatusclassicationsetover
thecondensedstate(Maintenancerequired/
Maintenance demanded:
,Outofspeci-
cation:
blinking, Maintenance alarm: ).
If 'No message' is assigned to the error code
asthestatusclassication,theerrorisnotin-
cluded in the condensed state.
Astatusclassicationisassignedtoevery
error code in the default setting. The assign-
mentofthestatusclassicationcanbe
changedinTROVIS-VIEWandoverthepa-
rametersoftheDD.Refertotheoperatingin-
structions for the valve diagnostics
uEB8389onEXPERTplusvalvediagnostics
for more details.
Toprovideabetteroverview,theclassied
messages are summarized in a condensed
state for the positioner according to the
NAMURRecommendationNE107.Thesta-
tus messages are divided into the following
categories:
Maintenance alarm
The positioner cannot perform its control
task due to a functional fault in the posi-
tioner itself or in one of its peripherals or
an initialization has not yet been suc-
cessfully completed.
Maintenance required
The positioner still performs its control
task (with restrictions). A maintenance
demand or above average wear has
been determined. The wear tolerance will
soon be exhausted or is reducing at a
faster rate than expected. Maintenance is
necessary in the medium term.
Maintenance demanded
The positioner still performs its control
task (with restrictions). A maintenance
demand or above average wear has
been determined. The wear tolerance will
soon be exhausted or is reducing at a
faster rate than expected. Maintenance is
necessary in the short term.
Out of specication
The positioner is running outside the
speciedoperatingconditions.
Ifaneventisclassiedas“Nomessage”,this
event does not have any affect on the con-
densed state.
Table15: Condensed state reading
Condensed state Positioner display
Maintenance alarm
Function check
Text e.g. TUNE or
TEST
Maintenancerequired/
maintenance demanded
Outofspecication
blinking
The message with the highest priority deter-
mines the condensed state in the positioner.
If fault alarms exist, the possible source of
error is displayed in Code 49 onwards. In
this case, ERR is displayed.

Table of Contents

Other manuals for Samson 373 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samson 373 Series and is the answer not in the manual?

Samson 373 Series Specifications

General IconGeneral
BrandSamson
Model373 Series
CategoryValve Positioners
LanguageEnglish

Related product manuals