Operating the positioner
7.1 Determining the fail-safe position
Denethefail-safepositionofthevalve(0%)takingthevalvetypeandtheactuator'sdirec-
tionofactionintoaccount.PositiontheAIRTOOPEN/AIRTOCLOSEslideswitchaccording-
ly:
− AIR TO OPEN setting
Signal pressure opens the valve, e.g. for a fail-close valve
TheAIRTOOPENsettingalwaysappliestodouble-actingactuators.
− AIR TO CLOSE setting
Signal pressure closes the valve, e.g. for a fail-open valve
For checking purposes: after successfully completing initialization, the positioner display
mustread0%whenthevalveisclosedand100%whenthevalveisopen.Ifthisisnotthe
case, change the slide switch position and re-initialize the positioner.
The switch position is prompted prior to an initialization. After an initialization has been
completed, changing the switch position does not have any effect on the operation of the po-
sitioner.
7.2 Adjusting the volume restriction Q
MIN SIDE
MIN BACK
Signal
pressure
Transit time
<1s ≥1s
Connection at the side MIN SIDE MAX SIDE
Connection at the back MIN BACK MAX BACK
* Intermediate settings are not permitted.
Fig.36: Volume restriction Q
The volume restriction Q serves to adapt the air output capacity to the size of the actuator:
− Actuators with a transit time < 1s, e.g. linear actuators with an effective area smaller
than240cm²,requirearestrictedairowrate(MIN).
− Actuators with a transit time ≥ 1sdonotrequiretheairowratetoberestricted(MAX).