EB 8384-2 EN 141
Appendix
Error codes – Recommended
action
Condensed state message active, when prompted, Err appears.
Whenfaultalarmsexist,theyaredisplayedhere.
76 No emergency mode The travel measuring system of the positioner has a self-monitoring
function(seeCode62).
An emergency mode (open-loop control) is not available for certain
actuators, such as double-acting actuators. In case of a travel sensing
error, the positioner vents the output (Output 38) or A1 in double-act-
ing actuators. During the initialization, the positioner automatically
checks whether the actuator has such a function or not.
Statusclassication [No message]
Recommendedaction Merelyinformation,conrm,ifnecessary.
No further action required.
77 Software loading error WhenthepositionerstartsoperationforthersttimeafterthePA
signal has been applied, it carries out a self-test (tEStinG runs across
the display).
If the positioner loads the wrong software, the valve moves to the fail-
safe position. It is not possible to make the valve leave this fail-safe
position again.
Statusclassication
Maintenancealarm(cannotbeclassied)
Recommendedaction
Interrupt current signal and restart the positioner.
If not successful, return positioner to SAMSON for repair.
78
Option parameters
Error in option parameters.
Statusclassication
[Maintenance required]
Recommendedaction
ReturnpositionertoSAMSONAGforrepair.