14 EB 8389-1S EN
Monitoring
− Resetting measured data does not cause
the diagnostic parameters and reference
value to be reset as well.
− The positioner does not need to be re-ini-
tialized after resetting.
Reset measured diagnostic data
Code 36 - Diag
− Parameters are reset as described in u
Section 17.4.
− Resets diagnostics assessment.
− Reference values remain unchanged.
− Status classication and data logs re-
main saved.
− The positioner does not need to be re-ini-
tialized after resetting.
− If the diagnostic data are to be reset at
regular intervals, enter the time in "De-
sired time until ‘Reset measured diagnos-
tic data" (Code 48 - h3). The setting
"00:00:00" causes the resetting at regu-
lar intervals to be deactivated.
Reset start-up parameters
Code 36 - Std
− Parameters are reset as described in
u Section 17.4.
− Resets diagnostics assessment.
− Reference values are deleted.
− Status classication remains unchanged.
− Data logs are reset.
− The positioner must be re-initialized after
resetting.
Reset to default settings
Code 36 - DS
− Parameters are reset as described in
u Section 17.4.
− Resets diagnostics assessment.
− Reference values are deleted.
− Status classication and data logs are
deleted.
− The positioner must be re-initialized after
resetting.
Note:
Before mounting the positioner on a
new control valve, perform a reset by
selecting the command 'Reset to de-
fault settings' (Code 36 - DS) and re-
initialize the positioner.