EB 8384-3 EN 16-9
Code
no.
Parameter–Readings/
values [default setting]
Description
39 Set point deviation e info
–99.9to99.9%
Read only
Indicatesthedeviationfromthetargetposition(e=w–x).
40 Transit time Open info
[0]to240s
Read only
Minimum opening time determined during initialization.
41 Transit time Closed info
[0]to240s
Read only
Minimum closing time determined during initialization.
42 Auto-w info
0.0to100.0%ofthe
span
Read only
Indicates the applied automatic set point with corresponding 4 to
20mAsignal.
43 Firmware info Read only
Indicatesthepositionertypeandcurrentrmwareversioninalter-
nating sequence.
44 y info
[0]to100%,0P,MAX,
–––
Read only
Indicatesthecontrolsignalyin%inrelationtothetravelrangede-
termined during initialization.
MAX: The positioner builds up its maximum output pressure,
seedescriptioninCode14and15.
0P: The positioner vents completely, see description in Code
14 and 15.
–––: The positioner is not initialized.
45 Solenoid valve info
YES,HIGH/LOW,No
Read only
Indicates whether a solenoid valve is installed or not.
If a voltage supply is connected at the terminals of the installed sole-
noid valve, YES and HIGH appear on the display in alternating se-
quence. If a voltage supply is not connected (actuator vented, fail-
safepositionindicatedonthedisplaybytheSicon),YESandLOW
appear on the display in alternating sequence.
46* Polling address
[0] to 63, ESC
Select bus address
47* Write protection HART
®
YES, [No], ESC
Whenwriteprotectionisactive,devicedatacanberead,butnot
overwritten over HART
®
communication.
48*
49*
Diagnostic parameters uEB8389