16-8 EB 8384-3 EN
Code
no.
Parameter–Readings/
values [default setting]
Description
32* Error message in case of
'Function check' con-
densed state
[YES], No, ESC
YES: Error message also in case of 'Function check' condensed
state
No: 'Function check' condensed state does not cause an error
message to be issued
Regardless of the condensed state, the fault alarm output always
switcheswhentheerrorcodes57,58,60,62and64to70,76are
issued.
33* Error message in case of
condensed state 'Mainte-
nance required'
[YES], No, ESC
YES: Error message only in case of condensed state
'Maintenance alarm' and 'Maintenance required'
No: Error message only in case of condensed state
'Maintenance alarm'
Regardless of the condensed state, the fault alarm output always
switcheswhentheerrorcodes57,58,60,62and64to70,76are
issued.
34* Closing direction
CL, [CCL], ESC
CL: Clockwise
CCL: Counterclockwise
Direction of rotation to reach the valve's CLOSED position (view onto
rotary switch with positioner cover open).
Needs only be entered in SUb initialization mode (Code 6).
35* Blocking position
[0.0]mm/°/%,ESC
Enter the blocking position (distance to CLOSED position)
Only necessary with SUb initialization mode.
36* Reset
[No], Std, diAG, ESC
Std: Resets all parameters and diagnosis data to their default
settings. After a reset, the positioner must be re-initialized.
diAG: Resets diagnosis data only. Plotted reference graphs and
logs remain saved.
The positioner does not need to be re-initialized.
37* Position transmitter
No, YES
Read only
Indicates whether an optional position transmitter is installed.
38* Inductive alarm
[No], YES, ESC
Indicates whether the inductive limit switch option is installed or not.