EasyManuals Logo

Samsung DVM Plus 2 Series User Manual

Samsung DVM Plus 2 Series
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #431 background imageLoading...
Page #431 background image
Troubleshooting
Samsung Electronics12-20
Is the suction sensor and
sensor holder correctly attached?
Is the resistance value of the
suction sensor proper?
(Refer to )
Reinsert the sensor
Reattach the sensor holder
The sensor defect :
Replace the sensor
Completion
No
No
Yes
Yes
: Suction Temperature Sensor Breakaway
1.
Check Method
Outdoor unit display
Indoor unit display (Operation) (Timer) (Fan) (Filter) (Defrost)
Suppose the Suction temperature right before Comp start that has high priority of start = Tsuc,
ini and the Suction temperature of current Comp = Tsuc, real. When | Tsuc, real - Tsuc, ini | <
2°C condition maintains for 30 minutes, the error is judged.
Causes Suction temperature sensor breakaway / sensor defect
Judgment method

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung DVM Plus 2 Series and is the answer not in the manual?

Samsung DVM Plus 2 Series Specifications

General IconGeneral
BrandSamsung
ModelDVM Plus 2 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals