EasyManuals Logo

Samsung mini DVM Series User Manual

Samsung mini DVM Series
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #515 background imageLoading...
Page #515 background image
Samsung Electronics14-19
Selecting additional refrigerant
• It depends on the total length of the liquid side pipe after the first Y-Joint.
• Example of calculating additional refrigerant : In case of 30HP outdoor unit
Liquid side pipe ø22.23
Total pipe length(m)x0.35
a : ø19.05x30m
b : ø15.88x10m
c : ø9.52x10m
d : ø9.52x10m
e : ø9.52x10m
f : ø9.52x10m
g : ø6.35x10m
h : ø6.35x10m
i : ø12.70x10m
j : ø6.35x10m
k : ø6.35 x 9m
Liquid side pipe ø19.05
Total pipe length(m)x0.27
Liquid side pipe ø15.88
Total pipe length(m)x0.18
A=
A= ++++= 14.33
30x0.27 10x0.18 10x0.125 40x0.06 49x0.02
+++
Liquid side pipe ø12.70
Total pipe length(m)x0.0125
Liquid side pipe ø9.52
Total pipe length(m)x0.06
Liquid side pipe ø6.35
Total pipe length(m)x0.02
++
14-5 Calculation for additional refrigerant