Control of W-ECO MULTI SYSTEM
3
TD831077
III - 43
2. Optional Controller (system controller)
7 How to set zone registration
To operate system controller properly, zone registration is required after finishing test run (after setting all indoor unit
addresses) as following methods.
(1) Zone registration by remote controller (RCS-SH80TG)
(2) Zone registration by system controller (SHA-KC64TG)
(3) Auto. zone registration by system controller (SHA-KC64TG)
In case of method (1) and (2), you should make the zone registration table manually in advance the above registration
as shown by next page.
In case of method (3), zone registration is executed automatically assigning from small indoor unit address and small
central address to large No. in numerical order. For example,
Central address 1 2 3 4 5 6
(ZONE–GROUP) 1-1 1-2 1-3 1-4 1-5 1-6
Indoor unit address 1-1 1-2 2-1 2-2 2-3 3-1
NOTE 1. Indoor unit address is assigned to each indoor unit after auto. address operation.
Indoor unit address is combined R.C. address and indoor unit No. as follows:
This address is displayed on remote controller for UNIT No. when pressing UNIT
button.
2. Central address represents each zone and group No. in numerical order.
---------------------------------------------------------------------------------------------------------------------------------------1
799 _8132
: Indoor unit address (UNIT No.)1–1
Indoor unit No.
Refrigerant circuit No. (R.C. address)