II - 33
2
TD831077
Design of W-ECO MULTI SYSTEM
4. Installation Instructions
4-11. Optional distribution joint kits
See the installation instructions packaged with the distribution joint kit for the procedure for installation.
Model Name Cooling capacity after distribution
1. APR-HV63MB1 16.0 kW (54.6 Mbtu/h) or less
2. APR-DV64MB
3. APR-DV94MB More than 16.0 kW (54.6 Mbtu/h)
4. APR-HV84MB 28.0 kW (95.5 Mbtu/h) or less
5. APR-HV106MB More than 30.0 kW (102.4 Mbtu/h)
52.4 kW (178.8 Mbtu/h) or less
6. APR-DV138MB More than 16.0 kW (54.6 Mbtu/h)
56.0 kW (191.1 Mbtu/h) or less
7. APR-DV148MB More than 28.0 kW (95.5 Mbtu/h)
101.0 kW (344.7 Mbtu/h) or less
8. APR-DV168MB More than 28.0 kW (95.5 Mbtu/h)
112.0 kW (382.2 Mbtu/h) or less
Insulation
1. APR-HV63MB1
Wide tube
103
210
E
E
D
ED
D
C
C
C
0015_M_I
Wide tube
120
80
1/2"1/2"
3/4"
140
374
60 60 60
1/2"
5/8"
0013_M_
I
86
3/8"3/8"3/8"3/8"
3/8"
324
60100 60 60
0014_M_I
Narrow tube
2. APR-DV64MB
Max. diameter 19.05 mm
Min. diameter 12.7 mm
3. APR-DV94MB
Max. diameter 28.58 mm
Min. diameter 19.05 mm
12.7–1)
Position A B C D E F G
Size 28.58 25.4 19.05 15.88 12.7 9.52 6.35
Unit: mm
Unit: mm
Position A B C D E F G
Size 28.58 25.4 19.05 15.88 12.7 9.52 6.35
Insulation
Narrow tube
83
185
GF E
FGE
E
F
G
0016_M_I
142
300
Outlet
Inlet
Outlet
CB A
ABC
A
B
C
D
E
0017_M_I
Wide tube
Insulation
Narrow tube
Insulation
83
185
GF E
FGE
E
F
G
0016_M_I
Max. diameter 12.7 mm
Min. diameter 6.35 mm
Max. diameter 12.7 mm
Min. diameter 6.35 mm