Control of W-ECO MULTI SYSTEM
3
TD831077
III - 25
2. Optional Controller (remote controller)
( I ) Set the indoor unit address
❏ This function is usable if the auto. address operation is not possible.
Indoor unit address can be set one by one by remote controller in such case.
1) In case of group control, branch wiring for group control should be removed temporarily.
2) In case of remote controller – less system, remote controller should be connected with the indoor unit
temporarily.
a Short the two terminals of DISP PIN on indoor unit PCB.
(DISP PIN : Refer to P. VI–2)
b Press the TEST / CHK , SET and CL buttons at the same time for more than 4 seconds.
c Set the CODE No. 12 to set the No. of R. C. with the