W-ECO MULTI SYSTEM Unit Spesifications
TD831077
IV - 18
4
MODEL No. SPW-C903GDCH8
Source 380 - 440 - 415 V / 3 N / 50Hz
Controller P.C.B. Ass’y CR - CR703GDH8
Control circuit fuse 250 VAC , 15 A
Compressor
SC (Scroll)
Model … Code No. C-SC753H8C ... 80975288
Nominal output kW 7.5
Compressor oil (ETHER FV68S) cc 2,700
Coil resistance V - U: 1.308
(Ambient temperature 25°C) U - W: 1.373
W - V: 1.351
Safety devices
Thermal protector ON / OFF °C 120 ± 5 / 98 ± 11
Microprocessor safety devices Compressor current detection circuit
Compressor discharge gas temperature control
Defective drop detection circuit
Voltage drop detection circuit
Crank case heater VAC, W 240, 44
Fusible plug (Operating temp) °C 73 ± 2
High pressure switch ACB - 1TB04W (TUV Approved)
Set pressure ON / OFF kg/cm
2
24 ± 2.0 / 33
Fan (Number … diameter(mm)) Propeller (1 … ø 750)
Fan motor
Model … Nominal output W KFJ8T - 301B3P… 200W
No. of pole … r.p.m. (230 V, High) 8 … 567 r.p.m.
Coil resistance BRN - WHT : 12.01
WHT - VLT : 4.218
VLT - YEL : 9.886
(Ambient temperature 20 °C) WHT - PNK : 12.65
Safety device
Thermal protector ON / OFF °C (115 ± 5) / 130 ± 5
Run capacitor VAC , µF 400 VAC , 17.5 µF
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows … fin pitch mm 2 … 1.8
Face area m
2
2.53
Outdoor Unit (H)
1. Outdoor Unit (For R22)

Table of Contents