W-ECO MULTI SYSTEM Unit Spesifications
TD831077
IV - 82
4
7. Concealed Duct Type
MODEL No. Indoor Unit SPW-UR253GHN56
POWER SOURCE 220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE Cooling Heating
Capacity kW 7.3 8.0
for Multi system (R22 and R407C)
BTU / h 25,000 27,000
Air circulation (Hi / Me / Lo) m
3
/ h 1,080 / 900 / 780
Moisture removal (High) Liters / h 3.5 —
External static pressure (High) Pa (mmAq) 50 (5.1): at shipment, 92 (9.4): using the booster cable
ELECTRICAL RATINGS
Voltage rating VAC 220 230 240 220 230 240
Available voltage range VAC 198 - 264
Running amperes
*
A 0.83 0.86 0.89 0.78 0.81 0.84
Power input W 180 195 210 168 183 198
Power factor % 98.6 98.6 98.3 97.9 98.2 98.2
Max. starting amperes A 1 1 1 1 1 1
FEATURES
Controls / Thermostat control Microprocessor / I.C. thermostat
Timer ON / OFF 72 hr
Fan speeds 3 and Automatic control
Air filter Field supply
Refrigerant control Electronic expansion valve
Operation sound (Hi / Me / Lo) dB-A 34 / 30 / 27
using the booster cable (Hi / Me / Lo)
dB-A 38 / 34 / 30
Refrigerant tubing connections Flare type
Refrigerant tube Narrow tube mm (in) 9.52 (3 / 8)
diameter
Wide tube mm (in) 15.88 (5 / 8)
Drain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32mm)
Remote controller (Option) Optional (RCS-SH80TG)
Color (Approximate value) –
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
Dimensions Height mm (in) 310 ( 12 - 7 /32) 358 (14 - 3 /32)
Width mm (in) 1,000 ( 39 - 12 /32) 1,191 ( 46 - 28 /32)
Depth mm (in) 630 ( 24 - 26 /32) 783 ( 30 - 26 /32)
Net weight kg (lb) 32 ( 71 )
Shipping weight kg (lb) 37 ( 82 )
Shipping volume m
3
(cu. ft) 0.334 ( 11.8 )
Unit specifications (D)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling :
Rating conditions (
*
) : Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DB
Heating :
Rating conditions (
*
) : Indoor air temperature 20 °C DB, Outdoor air temperature 7°C DB / 6°C DB