II - 8
Design of W-ECO MULTI SYSTEM
2
TD831077
1. Model Selecting and Capacity Calculation
1-4. Capacity correction graph according to temperature condition (For R407C)
Cooling Heating
Outdoor temp. Indoor temp.
Capacity Input
Outdoor temp. Indoor temp.
Capacity Input
(DB) (WB) coefficient coefficient (WB) (DB) coefficient coefficient
Indoor unit 25: a 33 ˚C 19 ˚C 100 % 95 % 0 ˚C 20 ˚C 89 % 92 %
Indoor unit 12: b 33 ˚C 19 ˚C 100 % 95 % 0 ˚C 20 ˚C 89 % 92 %
Indoor unit 9: c 33 ˚C 17.5 ˚C 90 % 81 % 0 ˚C 22 ˚C 86 % 94 %
Indoor unit 18: d 33 ˚C 17.5 ˚C 90 % 81 % 0 ˚C 22 ˚C 86 % 94 %
Indoor unit 36: e 33 ˚C 17.5 ˚C 90 % 81 % 0 ˚C 22 ˚C 86 % 94 %
05-5 10 15 20 25 30 35 40 45 50
70
80
90
100
110
120
10
20
30
40
50
60
80
90
100
110
120
130
Outdoor air intake temp. °C(DB)
Input coefficient (%) Capacity coefficient (%)
Indoor air intake temp. °C(WB)
Indoor air intake temp. °C(WB)
33
22°C
19
16
22°C
19
16
a. b
c. d. e
c. d. e
a. b
1285_M_I
-15
1286_M_I
-10 -5 0 5 10 15
70
80
90
100
40
50
60
110
120
40
50
60
70
80
90
100
110
120
130
Input coefficient (%) Capacity coefficient (%)
Indoor air intake temp. °C(DB)
Indoor air intake temp. °C(DB)
a. b
c. d. e
a. b
c. d. e
15°C
20
25
15°C
20
25
Outdoor air intake temp. °C (WB)
Cooling capacity diagram Heating capacity diagram
System example
¶ Heating capacity correction coefficient at the time of frosting / defrosting (For R407C)
Outdoor suction air temp
– 11– 10– 9– 8– 7– 6– 5– 4– 3– 2– 10123456
(CWB, RH85 %)
Correction coefficient
0.97 0.97 0.97 0.96 0.95 0.94 0.91 0.89 0.88 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
¶ To find out the heating capacity taking into account the frosting / defrosting operation, multiply the capacity given in the
capacity chart with the value in the above table.
¶ The correction coefficients are for outdoor capacity ratio 100 % heating operation.
Rating value: Cooling
Cooling capacity Input: kW
Model
:kW (Btu/h) 380 - 400 - 415 V
70 type 22.4 ( 76,400) 9.46 - 9.52 - 9.58
90 type 28.0 ( 95,500) 11.3 - 11.4 - 11.5
150 type 45.0 (154,000) 17.6 - 17.7 - 17.8
190 type 56.0 (191,000) 21.9 - 22.1 - 22.3
Rating value: Heating
Heating capacity Input: kW
Model
:kW (Btu/h) 380 - 400 - 415 V
70 type 25.0 ( 85,300) 9.08 - 9.12 - 9.17
90 type 31.5 (107,500) 10.6 - 10.8 - 11.0
150 type 50.0 (171,000) 16.9 - 17.0 - 17.2
190 type 63.0 (215,000) 20.6 - 21.0 - 21.4