Profibus Interface PR 5210 Operating Manual
54 Sartorius
6.2.11 Register 22 ... 27: Limit values (read/write)
Register 22 limit 1 on
Register 23 limit 1 off
Register 24 limit 2 on
Register 25 limit 2 off
Register 26 limit 3 on
Register 27 limit 3 off
6.2.12 Register 30: Analog output (read/write)
Register 30 Fixed value for analog output.
Value(num) 0... 40000
entspricht 20mA
6.2.13 Register 31: Fixtare (read/write)
Register 31 Fixed value for fixtare, see also SetFixTare,
GetFixTare ( see chapter 6.2.3)
6.2.14 Register 80 ... 93: Action bits state controlled (write)
Set bits, see chapter 6.1.5.3
Only setting and resetting of single bits are possible.
If a bit is changed from 0 to 1, the corresponding action is started. After execution of the command
the bit has to be reset. Application : Master is writing cyclically.
The bit is set with the shown number as Write_Value_Select (See chapter 6.1.5.3), with the shown
number+128 the bit is reset.
Register 80 SetZero Set gross to zero
Register 81 SetTare Execute taring
Register 82 ResetTare Reset tare
Register 83 SetTest Start ADU test
Register 84 ResetTest Terminate ADU test
Register 85 ResetPwf Reset bit PowerFail (register 1, bit has been set after power-on)
Register 86 SetFixTare Taring with weight in numerical address D 31 'Fixtare'
Register 87 GetFixTare The actual gross weight is copied to the numerical address D31
Register 89 ResetError The error bit CmdError will be reset
Register 90 SaveProcess The process data will be stored to EAROM
limit values (register 22...27)
fixed analog output value (register 30)
fixtare (register 31)
Register 91 SetParam Write parameter (value R20 to parameter R21)
Register 92 GetParam Read parameter (parameter R21 to R20)
Register 93 SaveConfig The configuration parameter will be stored to EAROM
analog output (parameter 1...3)
I/O parameter (parameter 4, 6)
input/output configuration (parameter 5, 7)
access control parameter (parameter 99)