EasyManua.ls Logo

Satec PM130 series - Extended Instrument Status

Satec PM130 series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
4.7 Extended Instrument Status
Table 4-11 Read Request
Message type (ASCII)
?
Message body (hexadecimal)
Request - no body
Response
Field Offset Length Parameter Range
1 0 4 Relay status see Table 4-12
2 4 4 Not used 0
3 8 4 Not used 0
4 12 4 Setpoints status see Table 4-13
5 16 4 Log status see Table 4-14
6 20 36 Not used 0
Table 4-12 Relay Status
Bit Description
0 Relay status
1-15 Not used (permanently set to 0)
Bit meaning: 0 = relay released, 1 = relay operated
Table 4-13 Setpoints Status
Bit Description
0 Setpoint # 1 status
1 Setpoint # 2 status
2 Setpoint # 3 status
3 Setpoint # 4 status
4 Setpoint # 5 status
5 Setpoint # 6 status
6 Setpoint # 7 status
7 Setpoint # 8 status
8 Setpoint # 9 status
9 Setpoint # 10 status
10 Setpoint # 11 status
11 Setpoint # 12 status
12 Setpoint # 13 status
13 Setpoint # 14 status
14 Setpoint # 15 status
15 Setpoint # 16 status
Bit meaning: 0 = setpoint is released, 1 = setpoint is operated
Table 4-14 Log Status
Bit Description
0 Reserved
1 New Min/Max log
2-15 Not used (permanently set to 0)
Bit meaning: 0 = no new logs, 1 = new log recorded (the new log flag is reset when the user reads the first
log record after the flag has been set)

Other manuals for Satec PM130 series