66 Appendix A Technical Specifications
Power Supply (factory set)
Galvanically isolated
120&230 V AC and
110&220 V DC
85-265VAC 50/60 Hz and 88-290VDC Burden 10 W
Option 12 V DC
Option 24 V DC
Option 48 V DC
9.6 - 19 VDC
19 - 37 VDC
37 - 72 VDC
Environmental Conditions
Operating temperature
-20°C to +60°C (-4°F to +140°F)
Storage temperature
-25°C to +80°C (-13°F to +176°F)
Humidity 0 to 95% non-condensing
Construction
Instrument body Case enclosure: Plastic PC/ABS blend
Dimensions: 127 x 127 x 127 mm ( 5.0 x 5.0 x 5.0 “)
Mounting: 4-inch round or 92x92mm square panel mount
Instrument weight 1.23 kg (2.7 lb.)
Display body Display body: plastic PC/ABS blend
Front Panel: plastic PC
Dimensions: 114.0x114.0x20.0 mm (4.5x4.5x.787”)
Standard Compliance
Standards UL File # E129258 (PENDING)
Directive Complied With: EMC: 89/336/EEC as amended by
92/31/EEC and 93/68/EEC
LVD: 72/23/EEC as amended by 93/68/EEC and 93/465/EEC
Harmonized Standards to which Conformity is Declared:
EN55011:1991; EN50082-1:1992; EN61010-1:1993; A2/1995
ANSI C37.90.1 1989 Surge Withstand Capability (SWC)
EN50081-2 Generic Emission Standard - Industrial Environment
EN50082-2 Generic Immunity Standard - Industrial Environment
EN55022: 1994 Class A
EN61000-4-2
ENV50140: 1983
ENV50204: 1995 (900MHz)
ENV50141: 1993
EN61000-4-4:1995
EN61000-4-8: 1993

Other manuals for Satec PM172EH series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Satec PM172EH series and is the answer not in the manual?

Satec PM172EH series Specifications

General IconGeneral
BrandSatec
ModelPM172EH series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals