Appendix A Technical Specifications 69
Accuracy, % Parameter
Full scale
Rdg FS Conditions
Range Display resolution (%Rdg)
@
range
2
Harmonic active
power
0.36×PT×CT @ 120V input
1.2×PT×CT @ 690V input
1.5
2.0
1.0
1.0
PF = 1
|PF| 0.5
3
-2,000,000 to
+2,000,000 kW
Direct wiring (PT=1):
0.001 kW
@
0.001kW to 9.999 kW
Wiring via PTs (PT>1):
0.001 MW
@
0.001MW to 9.999 MW
0.1%
@
10.00 MW to 2000 MW
Harmonic apparent
power
0.36×PT×CT @ 120V input
1.2×PT×CT @ 690V input
1.5 1.0
3
0 to
2,000,000 kVA
Direct wiring (PT=1):
0.001 kVA
@
0.001kVA to 9.999 kVA
Wiring via PTs (PT>1):
0.001 MVA
@
0.001MVA to 9.999 MVA
0.1%
@
10.00 MVA to 2000 MVA
Voltage & Current
harmonic angles,
degree
360°
0.6° + 0.5° ×
harmonic order
3
-180° to 180° N/A
Active energy
Import & Export
Class 0.5S (IEC 687-1992-6) 0 to
999,999 MWh
1 kWh
@
1 to 999,999 kWh
10 kWh
@
1000 to 9,999.99 MWh
100 kWh
@
10,000 to 99,999.9 MWh
1MWh
@
100,000 to 999,999 MWh
Reactive energy
Import & Export
Under conditions of Class 1.0
(IEC 1036)
|PF| 0.9
1
0 to
999,999 Mvarh
1 kvarh
@
1 to 999,999 kvarh
10 kvarh
@
1000 to 9,999.99 Mvarh
100 kvarh
@
10,000 to 99,999.9 Mvarh
1Mvarh
@
100,000 to 999,999 Mvarh

Other manuals for Satec PM172EH series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Satec PM172EH series and is the answer not in the manual?

Satec PM172EH series Specifications

General IconGeneral
BrandSatec
ModelPM172EH series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals