EasyManua.ls Logo

Satel Versa Seris - Connecting the Hardwired Zone Expanders

Satel Versa Seris
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SATEL VERSA 15
Depending on the controller, set the DIP-switches as required:
ACU-120 / ACU-270: switch 8 to ON position, the status of the other switches being
irrelevant,
ACU-100: switches 4, 7 and 8 to ON position, and the other ones to OFF position (address 8
(08h) and the VERSA control panel compatibility mode enabled),
ACU-250: switch 4 to ON position, and the other ones to OFF position (address 8 (08h)).
All controllers of the ABAX wireless system are identified by the control panel as the
ACU-100 controller.
If the ACU-120 / ACU-270 / ACU-100 / ACU-250 controller is connected to the control
panel, installation of the VERSA-MCU controller in the system is impossible.
Fig. 13. Setting the DIP-switches in the ACU-120 / ACU-270 controller.
Fig. 14. Setting the DIP-switches in the ACU-100 controller.
5.5.6 Connecting the hardwired zone expanders
Fig. 15. Connecting the INT-E expander to the control panel.
Up to three INT-E / CA-64 E / CA-64 EPS expanders can be connected to the control panel.
This enables expansion of the system by adding up to 24 programmable wired zones. Using
the expander DIP-switches:
set an address within the range from 12 (0Ch) to 14 (0Eh) – switches 1-5,
define how the expander is to be identified – switch 10 (INT-E) or 8 (CA-64 E /
CA-64 EPS).

Table of Contents

Related product manuals