8OPERATION
8.2.2 Exprt mode
The Exprt mode offers the full functionality of the display.
Advanced functions are available for:
Switching outputs
Output: Process variable, hysteresis/window, polarity, simulation, electrical
property (NPN / PNP / DRV (push-pull))
Using the switching output as input for initiating actions (minLvl, maxLvl, etc.)
Analog outputs
Switching the process variable, 4–20 mA/0–10 V, error signal, simulation
Conguration
Display, units, offset, lock
Measurement
Detailed signal quality, lter, TrsHld
Note:
Exprt mode is automatically activated when IO-Link is used.
8.3 Conguring the switching outputs
8.3.1 Switching hysteresis and window function
2 or 4 outputs depending on variant
Level
t
SP
RP
high
low
high
low
HNO
HNC
If the level is uctuating around the set
value (e.g., ripple movement during ll
-
ing), the hysteresis keeps the switching
status of the outputs stable. When the
level is increasing, the output switches
when the respective switching point
(SP) is reached; if the level sinks again,
the output switches back only after the
reset switching point (RP) has been
reached.