14TECHNICAL DATA
14.7 Electrical connections
Supply voltage
1)
DC 10 V ... 30 V
Current consumption ≤ 100 mA at 24 V without output load
Initialization time ≤ 5 s
Protection class III
Connection type M12 x 1 (5-pin)
M12 x 1 (8-pin)
Hysteresis Min. 3 mm, min. 2 °C, freely congurable
Output signal
2)
• 2 switching outputs PNP/NPN/DRV
• 2 switching outputs PNP/NPN/DRV and 1
analog output 4 mA to 20 mA / 0 V to 10 V auto-
matically switchable depending on output load
• 4 switching outputs PNP/NPN/DRV and 2 ana-
log outputs 4 mA to 20 mA / 0 V to 10 V auto-
matically switchable depending on output load
Signal voltage HIGH Uv –3 V
Signal voltage LOW ≤ 3 V
Output current < 100 mA per output
Inductive load < 1 H
Capacitive load 100 nF
Temperature drift < 0.1 mm/K
Output load 4 mA to 20 mA < 500 ohms at U
v
> 15 V
4 mA to 20 mA < 350 ohms at U
v
> 2 V
0 V to 10 V > 750 ohms at U
v
≥ 14 V
Lower signal level 3.8 mA to 4 mA
Upper signal level 20 mA to 20.5 mA
EMC EN 61326-2-3, 2014/30/EU
1)
Use an energy-limited circuit for voltage supply as per UL61010-1 3rd Ed., Section 9.3.
2)
All connections are reverse polarity protected. All outputs are overload and short-circuit
protected.