OPERATING INSTRUCTIONS | CFP CUBIC 8021989 / 2017-10-20 | SICK AG
Subject to change without notice
30
8 OPERATION
• Invert = Analog output signal is inverted; QaHigh 0 V and QaLow 10 V
6. Select electrical signal.
Set the parameter in the QA-### / QATYP menu to 0–10 V.
8.4.4 Behavior of outputs in the event of an error
Conguration
Note:
The analog output designation (QA in the example here) changes according to the se-
lected process variable to be output.
This function is only available if 4 to 20 mA is selected under QA-TYP.
1. Log in to Exprt mode, see “8.2.2 Exprt mode”.
2. Select electrical signal.
• Select the parameter in the QA-### / QA-TYP menu and set the value to 4 to
20 mA.
3. Dene the signal in the event of an error.
• Select the parameter in the QA-### / QA-FAIL menu and set to the required
value.
8.5 Advanced functions
8.5.1 Selecting display unit
The following units can be selected for the measured values:
− UnitLv: mm, inch
− UnitTm: °C, °F
Conguration
1. Log in to Exprt mode, see “8.2.2 Exprt mode”.
2. Set the unit for level.
• Set the unit in the CONFIG / UNITLV menu (mm/inch).
Or
1. Log in to Exprt mode, see “8.2.2 Exprt mode”.
2. Set the unit for temperature.
• Set the unit in the CONFIG / UNITTM menu (°C/°F).
8.5.2 Setting an alternating display of measurands (DispA and DispB)
Up to two measured values can be displayed alternately.
Function Description
Level Level in mm/inch
Level % Level in %
Temp
1)
Temperature in °C/°F
QaSign
1)
Qa analog output signal in mA/mV