OPERATING INSTRUCTIONS | CFP CUBIC 8021989 / 2017-10-20 | SICK AG
Subject to change without notice
24
8 OPERATION
6. Set the switching point.
Set the value in the Q1-### / SP1 menu to level in mm (e.g., 500 mm).
7. Set the reset point.
Set the value in the Q1-### / RP1 menu to level in mm (e.g., 450 mm).
8. Select the electrical property (NPN/PNP/DRV [push/pull]).
Select the parameter in theQ1-LVL / TYP1 menu.
The following rules apply:
PNP = Switching output in PNP circuit
NPN = Switching output in NPN circuit
DRV = Switching output in push/pull function
Switching output behavior
Level
t
SP
RP
active
disabled
Error signal
Switching output PNP NPN DRV Error status
Normally closed/
HNC
active U
v
0 V U
v
(PNP switched) disabled
disabled 0 V
1)
U
v
2)
0 V (NPN switched)
1)
Pulldown only
2)
Pullup only
8.3.4 Normally open with window function
Application
Thecritical lling level for the application is within the FHx and FLx window thresholds.
Conguration
Congure the Qx switching output as normally open (using Q1 as an example).
Note:
The switching output designation (Q1 in the example here) changes according to the
selected process variable to be output.
1. Log in to Exprt mode, see “8.2.2 Exprt mode”.