OPERATING INSTRUCTIONS | CFP CUBIC 8021989 / 2017-10-20 | SICK AG
Subject to change without notice
22
8 OPERATION
2 or 4 outputs depending on variant
Level
t
FH
FL
high
low
high
low
FNO
FNC
The window function enables monitor-
ing of a dened range. If the level is
between window high (FH) and window
low (FL), the output will be active
(normally open) or inactive (normally
closed).
The error status of the measuring
device reects the cable break monitor-
ing. During an error status, the measur-
ing device switches to a safe state; i.e.
the switching outputs become inactive.
As far as the downstream signal evalu-
ation is concerned, this corresponds to
a cable break.
8.3.2 Normally open with congurable hysteresis
Applications
Dry run protection
Empty signal
Conguration
Congure the Qx switching output as normally open (using Q1 as an example).
Note:
The switching output designation (Q1 in the example here) changes according to the
selected process variable to be output.
The following conguration is only possible if the value is set to LEVEL or TEMPER under
PROC1.
1. Log in to Exprt mode, see “8.2.2 Exprt mode”.
2. Congure the switching output as output in the Q1-### / MODE1 / OUTPUT menu.
3. Congure the process variable to be output.
Set the value to LEVEL or TEMPER in the Q1-### / PROC1 menu.
4. Set the Hysteresis mode in the Q1-### / OUT1 / HYST. menu.
Set the parameter to NO in the Q1-### / POL1 menu.
5. Set the switching point.
Set the value in the Q1-### / SP1 menu to level in mm (e.g., 500 mm).
6. Set the reset point.
Set the value in the Q1-### / RP1 menu to level in mm (e.g., 450 mm).
7. Select the electrical property (NPN/PNP/DRV [push/pull]).
Select the parameter in the Q1-### / TYP1 menu.
The following rules apply: