OPERATING INSTRUCTIONS | CFP CUBIC8021989 / 2017-10-20 | SICK AG
Subject to change without notice
25
8OPERATION
2. Set the Output mode in the Q1-### / MODE1 / OUTPUT menu.
3. Congure the process variable to be output.
• Set the parameter to the required value in the Q1-### / PROC1 menu.
4. Set the Window mode in the Q1-### / OUT1 / WINDOW menu.
5. Congure the switching output as normally open.
• Set the parameter to NO in the Q1-### / POL1 menu.
6. Set the switching point.
• Set the value in the Q1-### / FH1 menu to level in mm (e.g., 500 mm).
7. Set the reset point.
• Set the value in the Q1-### / FL1 menu to level in mm (e.g., 400 mm).
8. Select the electrical property (NPN/PNP/DRV [push/pull]).
Select the parameter in the Q1-### / TYP1 menu.
The following rules apply:
• PNP = Switching output in PNP circuit
• NPN = Switching output in NPN circuit
• DRV = Switching output in push/pull function
Switching output behavior
Level
t
FH
FL
active
disabled
Error signal
Switching output PNP NPN DRV Error status
Normally open/FNO
active U
v
0 V U
v
(PNP switched)
disabled
disabled 0 V
1)
U
v
2)
0 V (NPN switched)
1)
Pulldown only
2)
Pullup only
8.3.5 Normally closed with window function
Application
The critical lling level for the application is outside the FHx and FLx window thresholds.