8 OPERATION
Conguration
Congure the Qx switching output as normally closed (using Q1 as an example).
Note:
The switching output designation (Q1 in the example here) changes according to the
selected process variable to be output.
1. Log in to Exprt mode, see “8.2.2 Exprt mode”.
2. Set the Output mode in the Q1-### / MODE1 / OUTPUT menu.
3. Congure the process variable to be output.
Set the parameter to the required value in the Q1-### / PROC1 menu.
4. Set the Window mode in the Q1-### / OUT1 / WINDOW menu.
5. Congure the Q1 switching output as normally closed.
Set the parameter to NC in the Q1-### / POL1 menu.
6. Set the switching point.
Set the value in the Q1-### / FH1 menu to level in mm (e.g., 500 mm).
7. Set the reset point.
Set the value in the Q1-### / FL1 menu to level in mm (e.g., 400 mm).
8. Select the electrical property (NPN/PNP/DRV [push/pull]).
Select the parameter in the Q1-### / TYP1 menu.
The following rules apply:
PNP = Switching output in PNP circuit
NPN = Switching output in NPN circuit
Drv = Switching output in push/pull function
Switching output behavior
Level
t
FH
FL
active
disabled
Error signal