Table 133: Faults in the safety capable inputs (I)
Fault Responses Causes
Electro-mechanical
s
witch/safety switch
(EMSS), safety sen‐
sors with test input,
Flexi Loop: safety
capable input is Low
instead of High
Pr
ocess data bit of the affected
input = 0
Short-circuit to another line
e.g., GND
Error in the sensor
Line break
Electro-mechanical
s
witch/safety switch
(EMSS), safety sen‐
sors with test input,
Flexi Loop: test
pulses from the asso‐
ciated test output
X are not detected
correctly (short-circuit
detection)
Pr
ocess data bit of the affected
input = 0
Status Ix process data status bit =
0
Module status bit of the affected
Status Ix input = 0
Short-circuit to other volt‐
age-carrying line
Error in the sensor (for exter‐
nally tested sensors)
Dual-channel elec‐
t
ro-mechanical safety
switch (EMSS), safety
sensors with moni‐
tored semiconductor
outputs (OSSD): equiv‐
alent/complementary
safety capable inputs
exhibit different/the
same values.
Pr
ocess data bit of the affected
input = 0
Status Ix, ly dual-channel evaluation
process data status bit = 0
Module status bit of the affected
Status Ix, ly dual-channel evaluation
input = 0
Short-circuit to another line
e.g., GND
Error in the sensor
Line break
Discrepancy time
Sequence error
Safety pressure mats:
s
afety capable input
is Low instead of test
pulse signal from the
associated test output
X
Pr
ocess data bit of the affected
input pair = 0
Status Ix process data status bit =
0
Module status bit of the affected
Status Ix input = 0
Line break
Test output sensor
Line break
Sensor s
afety capable
input
Safety pressure mats:
s
afety capable input is
High instead of test
pulse signal from the
associated test output
X
Pr
ocess data bit of the affected
input = 0
Status Ix, ly dual-channel evaluation
process data status bit = 0
Module status bit of the affected
Status Ix, ly dual-channel evaluation
input = 0
Short-circuit to other volt‐
age-carrying line
Internal error detected
in in
put evaluation
S
afety controller switches to the
critical error status
Internal error module status bit = 0
Internal device error
Table 134: Faults in the safety outputs (Q)
Fault Responses Causes
Output voltage level
is L
ow instead of
High when the output
is “On”, overload/over‐
current
1)
2)
A
ssociated output/associated
output pair is switched off
Depending on the load, the
affected output may pulsate tem‐
porarily until the final switch-off
Status Qx short-circuit to Low process
data status bit = 0
Status Qx short-circuit to Low module
status bit = 0
Short-circuit or resistance
drop under load
Short-circuit to another line
e.g., GND
11 TROUBLESHOOTING
122
O P E R A T I N G I N S T R U C T I O N S | Flexi Compact 8024589/2020-11-10 | SICK
Subject to change without notice

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK Flexi Compact and is the answer not in the manual?

SICK Flexi Compact Specifications

General IconGeneral
BrandSICK
ModelFlexi Compact
CategoryController
LanguageEnglish

Related product manuals