Principle of operation
T
able 48: Inputs
Input Description
Control Data type: Boolean
Table 49: Outputs
Output Description
Enable Data type: Boolean
D
epending on the On delay time parameter.
Table 50: Parameter
Parameter Description
On delay time 0 … 300 s in 1-ms steps
1)
•
The delay time begins with a rising signal edge at the Control input.
If, after expiration of the configured delay time, the Control input is
still 1, the Enable output = 1.
•
If the Control input returns to 0 before expiration of the configured
switch-on delay time, the Enable output remains = 0. The timer for
the switch-on delay time is reset to 0.
1)
0 = No delay
Complementary information
If t
he configured delay time is less than or not a multiple of the logic execution time,
then the delay time extends to the next logic cycle.
If, during the first logic cycle, the Control input = 1 and a switch-on delay time > 0 is
configured, then the Enable output = 0. If the Control input remains at 1, then the Enable
output remains 0 until the configured switch-on delay time has expired (Prerequisite:
First logic cycle < configured switch-on delay time).
7.6.2.3.2 Fixed off-delay timer V1
Overview
T
he function block delays switch-off of the Enable output by a configurable period of
time if a falling signal edge is present. The output is switched on without delay if a rising
signal edge is present.
Principle of operation
Table 51: Inputs
Input Description
Control Data type: Boolean
Table 52: Outputs
Output Description
Enable Data type: Boolean
D
epending on the Off delay time parameter.
7 CONFIGURATION
64
O P E R A T I N G I N S T R U C T I O N S | Flexi Compact 8024589/2020-11-10 | SICK
Subject to change without notice