Procedure:
1. Connect the communication interface (e.g., Ethernet) of the device directly to the
computer using a cable 9.
2. If external antennas are used (maximum 3, e.g., RFA630-000), these must be
connected to the antenna inputs of the device using connecting cables à.
3. Connect "Connection 1" (male connector, M12, 17-pin, A-coded) of the device to
the corresponding female connector on the connection module using a cable ß.
4. If necessary, connect a trigger sensor for the external read cycle, such as a
photoelectric retro-reflective sensor, to the “Sens/IN 1” (CDB650-204) or “Sensor
1” (CDM420-0006) digital input of the connection module. For CDB650-204:
see "Wiring digital inputs of the device in the CDB650-204", page 106. For
CDM420-0006: see "Wiring digital inputs of the device in the CDM420-0006",
page 119.
5. Supply the device with the required voltage depending on the length of the con‐
necting cable ß, see "Supply voltage", page 51.
✓
After successful initialization, the “Device Ready” LED lights up green.
6. Switch on computer.
7. Start Windows.
RFU630-041xx (without internal antenna)
...
...
1
2
V
S
GND
"Ethernet" (AUX 2)
...
1 4
RFU630-
041xx
"Power/Serial Data/CAN/I/O"
(AUX 1, Host 1)
External antennas á
8
Cable 9
Cable ß
Cable à
2
3
Connection
module
EthernetEthernet
Configuration
Reading result
display
Transponder
access
Reading
diagnostics
Cable 4
"USB" (AUX 3),
for temporary use only 6
SerialSerial
USBUSB
SOPAS ETSOPAS ET
Computer
"Serial RS-232" (AUX 1) 5
Cable 7
SGND
+24 V*
37 38 39
Sensor 1
Trigger
sensor
1
Out
GND
V
S
CDM420-0006
SGND
U
IN
*
10 11 12
Sens/IN 1
Trigger
sensor
1
Out
GND
V
S
CDB650-204
Figure 30: Electrical connection block diagram for the RFU630-041xx with optional connection
module: commissioning
1
Trigger sensor for external read cycle
2
Supply voltage V
S
3
Connection module CDB650-204 or CDM420-0006
4
Null modem cable with two female connectors, D-Sub, 9-pin, crossed TxD and RxD
5
Serial RS-232, alternative to USB or Ethernet AUX port
6
USB, alternative to serial RS-232 or Ethernet AUX port The USB interface must only be
used temporarily as a servicing interface.
7
Adapter cable with male connector, USB, type Micro-B and male connector, USB, type A
8
Configuration with SOPAS ET, prepared representation of the read result, transponder
access or reading diagnostics
9
Adapter cable with male connector, M12, 4-pin, D-coded and male connector, RJ-45,
8-pin
COMMISSIONING 7
8027750//2022-12-15 | SICK O P E R A T I N G I N S T R U C T I O N S | RFU63x