Voltage-Balance Supervision
Setting Values
Release threshold 0.300 V to 170.000 V Increments of 0.001 V
Threshold min/max 0.58 to 0.95 Increments of 0.01
Delay failure indication 0.00 s to 100.00 s Increments of 0.01 s
Dropout Ratio
Overvoltage dropout ratio Approx. 0.97
Undervoltage dropout ratio Approx. 1.05
Times
Tripping time Approx. 500 ms
Dropout time Approx. 500 ms
11.38
Technical Data
11.38 Voltage-Balance Supervision
1186 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017