Figure 6-17
Routing of the 1-Pole in DIGSI
The meaning of abbreviations can be found in Table 6-8 and Table 6-9.
The indication Command active can also be routed to a binary output. This binary output is always active if
either an On or trip command is pending, or the switching device was selected by the command control.
Settings
Addr.
Parameter C Setting Options Default Setting
Ref. for %-values
_:2311:101 General:Rated
normal current
0.20 A to 100000.00 A 1000.00 A
_:2311:102 General:Rated
voltage
0.20 kV to 1200.00 kV 400.00 kV
Breaker settings
_:2311:112 General:Current
thresh. CB open
1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:2311:113 General:1-pole
operate allowed
•
no
•
yes
yes
6.2.2.4
Control Functions
6.2 Switching Devices
SIPROTEC 5, High-Voltage Bay Controller, Manual 321
C53000-G5040-C015-9, Edition 11.2017