Addr. Parameter C Setting Options Default Setting
_:661:17 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:23 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: Cold load PU
_:661:33 Definite-T 1:Effect. b.
cold-load pickup
•
no
•
yes
no
_:661:40 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:661:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:24 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: bin.input
_:661:34 Definite-T 1:Effected by
binary input
•
no
•
yes
no
_:661:41 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:661:19 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:25 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Information List
No.
Information Data Class
(Type)
Type
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:661:81 Definite-T 1:>Block stage SPS I
_:661:84 Definite-T 1:>Activ. dyn. settings SPS I
_:661:500 Definite-T 1:>Block delay & op. SPS I
_:661:54 Definite-T 1:Inactive SPS O
_:661:52 Definite-T 1:Behavior ENS O
_:661:53 Definite-T 1:Health ENS O
7.4.4.4
Protection and Automation Functions
7.4 Overcurrent Protection, Phases
SIPROTEC 5, High-Voltage Bay Controller, Manual 611
C53000-G5040-C015-9, Edition 11.2017

Table of Contents