Parameter Value Description
via control
The switchover between the settings groups can only be initiated via a
communication connection from a substation automation technology or via
a CFC chart.
The communication protocols IEC 60870-5-103, IEC 60870-5-104, IEC
61850, DNP or Modbus TCP can be used for switching the settings groups
via a communication connection.
via binary input
The switchover between the settings groups functions exclusively via the
binary input signals routed to the settings group switching.
settings group 1
...
settings group 8
They define the active settings groups. You can define the active settings
groups in DIGSI 5, or directly on the device via the on-site operation.
Settings
Addr. Parameter C Setting Options Default Setting
Change group
_:113 General:Number settings
groups
1 to 8 1
_:114 General:Activat. of
settings group
•
via control
•
via binary input
•
settings group 1
•
settings group 2
•
settings group 3
•
settings group 4
•
settings group 5
•
settings group 6
•
settings group 7
•
settings group 8
settings group 1
Information List
No.
Information Data Class
(Type)
Type
General
_:500 General:>SG choice bit 1 SPS I
_:501 General:>SG choice bit 2 SPS I
_:502 General:>SG choice bit 3 SPS I
_:300 General:Act. settings group 1 SPC C
_:301 General:Act. settings group 2 SPC C
_:302 General:Act. settings group 3 SPC C
_:303 General:Act. settings group 4 SPC C
_:304 General:Act. settings group 5 SPC C
_:305 General:Act. settings group 6 SPC C
_:306 General:Act. settings group 7 SPC C
_:307 General:Act. settings group 8 SPC C
General Device Settings
Overview
In Device settings in DIGSI 5, you find the following general settings.
3.10.1.5
3.10.1.6
3.10.2
3.10.2.1
System Functions
3.10 Device Settings
164 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017