Figure 8-33 Structure/Embedding of the Function
Function Description
Errors in the current circuits are detected if
I
F
= |iA + iB + iC + iN| > Threshold value + Slope of the characteristic 1 •Σ| i | and
I
F
> Slope of the characteristic 2 • (Σ| i | - Base point 2)
With the current inputs (iA, iB, iC, and iN), the device calculates:
The fault current I
F
= |iA + iB + iC + iN|
The maximum current Σ| i | = |iA|+|iB|+|iC| + |iN|
[lokenisu-240413-01.tif, 2, en_US]
Figure 8-34 Characteristic Curve of the Supervision of the Device-Internal Analog-Digital Converters
8.4.2.3
Supervision Functions
8.4 Supervision of the Device Hardware
SIPROTEC 5, High-Voltage Bay Controller, Manual 977
C53000-G5040-C015-9, Edition 11.2017